headerimage
KHA6-SH-Ex1

KHA6-SH-Ex1
Isolation amplifiers (intrinsically safe)

Service intended: Isolation amplifier with intrinsically safe control circuit class [EX ia] II C for double inductive contacts to DIN 19234 respectively NAMUR or mechanical contacts for hazardous area industrial equipment.
 

hr
Downloads
Technical Details
Operation Manual
Declaration of conformit
Technical Data
Case material
Macrolon
Case dimensions
40 x 93 x 115 mm
Mounting
Snap mounting on rail : 35 mm to EN 50022
Weather protection
IP 20 to EN 60529
Wiring
Self-opening instrument terminals, Cable cross section : up to 2,5 mm2
Power supply
AC 85 - 253 V / 45 - 65 Hz
Power consumption
≤ 2,3W
Inputs (intrinsically safe)

No load voltage UA0 : approx. 8,4 VDC
Short circuit current IAK : approx. 11,7 mA
Switching point
Relay energised : 2,8 mA < IS < 5,3 mA
Relay de-energised : IS <2,8 mA or ≥5,9mA

Input delay : ≤ 1 ms

Details of certificate of conformity
PTB 00 ATEX 2081
Max. voltage U0 : 9,6 VDC
Max. current IK: 19mA
Max. power Pmax : 45 mW
Ignition protection class : [Ex ia]
Explosion group : IIC
Outputs (non-intrinsically safe)

2 potential free make contact
Contact loading AC : 253 V / 1 A

                            : cosφ= 0,7
Contact loading DC : 24 V / 1 A

Switching rate
Max. : 5Hz
Permissible temperatures Tmin / Tmax
Ambient temperature: - 20 ... + 60°C
Order-No.
390765